*Rescheduled notice of monthly generator testing
| Affected location(s): | Woodsworth College Residence (130) |
| Service period: | Thursday, Jan. 16, 2025 Thursday, Feb. 20, 2025 Thursday, Mar. 20, 2025 Friday, Apr. 4, 2025 Monday, May. 5, 2025 Friday, Jun. 6, 2025 Monday, Jul. 7, 2025 Thursday, Aug. 7, 2025 Friday, Sep. 5, 2025 Monday, Oct. 6, 2025 Monday, Nov. 3, 2025 Friday, Dec. 5, 2025 |
What is being done and why?
Brief electrical shutdowns are scheduled so that monthly testing can be done on life safety generators. To learn more about why F&S does monthly generator tests, visit our emergency generator resource page.
How will it impact building occupants?
- All receptacles, lighting, and equipment that are connected to emergency power will be shut down twice for up to 15 seconds each time.
- The first outage is estimated to take place at 2 PM. The second outage is estimated to take place between 3 PM and 3:30 PM.
- Receptacles, lighting, and equipment that are connected to normal power will not be affected.
- In addition, the following specific equipment and/or areas that are connected to emergency power will be impacted:
Panel EP (Located in AV Storage Room)
- All Emergency Lighting, Exit Signs, and Receptacles.
Panel LP-8EA (Located in 8th Floor Elec/Telecom Room)
- All Emergency Lighting, Exit Signs, and Receptacles.
- Motorized Dampers 5-12
- Motorized Dampers 13-17
- Motorized Damper Control
Panel LP-18E (Located in Penthouse Generator Room)
- All Emergency Lighting, Exit Signs, and Receptacles.
Panel LP-18EA (Located in Penthouse Generator Room)
- All Emergency Lighting, Exit Signs, and Receptacles.
- Generator Room Receptacles
- Freon Detector
- Generator Battery Charger
- Generator Block Heater
- Mech Room. Motorized Damper
- Elevator Machine Room Receptacle
- BAS Control Panel
- Elevator #1
- Elevator #2
Panel LP-BE (Located in Mech Room 90/ Room 38)
- All Emergency Lighting, Exit Signs, and Receptacles.
- SPF #1
- Sprinkler Compressor
- Condensate Receptacle Pump
- SPF #3
- Splitter PP-BE1
Panel LP-BEA (Located in Mech Room 90/ Room 38)
- All Emergency Lighting, Exit Signs, and Receptacles.
- Fire Alarm System
- BAS
Panel LP-BEB (Located in H.V. Substation)
- All Emergency Lighting, Exit Signs, and Receptacles.
- Condensate Pump Set CFU-1
- Data Rack Receptacle
- Transformer #1 Fan
- Transformer #2 Fan
- Dampers
- Diesel Fuel Pumps
- Elevator #4 Cab lights
- EF-2, EF-3 receptacles
- Storm Pumps
- Sanitary Pumps
- Glycol Pump
Who do I contact for more information?
If you have questions or concerns about this life safety generator testing, please contact Cheung Chow, P.Eng., electrical systems engineer at [email protected].
Issued by
Cheung Chow, P.Eng.
Electrical Systems Engineer